Acidic, metal-laden water is one of the most persistent legacies of mining. Long after extraction has stopped, ponds on former mine sites can keep producing water that must be neutralised before it is released to the environment. Lime remains the reagent of choice for this job — but only if it can be stored, extracted and dosed reliably.
The Challenge
The site in this case study is a former gold and silver mine in a region known for harsh winters and wide temperature swings. Water collected in on-site ponds had to be treated for pH before being discharged to downstream rivers. The operator needed a lime system that could run with minimal attention, in difficult weather, and deliver a consistent dose to the treatment process.
Hydrated lime is a fine, cohesive powder. Left alone in a silo, it tends to compact, absorb moisture and form bridges or "rat-holes" above the outlet. When that happens, the dosing rate drops or stops altogether, and pH control is lost. In a remote installation, an unreliable lime line quickly becomes the weakest link of the whole treatment chain.
The Solution
The equipment manufactured by Sodimate for this project was a complete lime storage and handling system: two storage silos, mechanical discharge at the base of each silo, volumetric screw feeding, and a lime slurry preparation tank producing milk of lime at a concentration of around 15%.
A key element of the design is the operating logic between the two silos. Each silo is fitted with three level detectors (high, medium and low). When both silos are full and one of them reaches its medium level, operation switches to the fuller silo. The aim is simple: reduce the time lime spends sitting in storage, which limits compaction and the risk of flow problems.
Equipment Breakdown
- Twin storage silos — providing buffer capacity and redundancy, so that one silo can be refilled or serviced while the other continues to feed the process.
- Mechanical silo dischargers — mechanical bin activators at the silo outlets keep the lime flowing and prevent bridging, which is the most common cause of dosing interruptions with hydrated lime.
- Level detection — high, medium and low level switches on each silo drive the alternating operation and give the operator a clear view of available stock.
- Volumetric screw feeder — the screw meters the lime at a controlled rate and transfers it, via an inclined conveyor, to the slurry tank.
- Lime slurry tank — the powder is mixed with water to produce a lime slurry at approximately 15%, which is then dosed into the water to be treated.
Each of these components is standard in Sodimate's range; the value lies in how they are combined and controlled as a single, coherent system rather than as separate pieces of equipment from different suppliers.
Results
According to the published project summary, the installation has proven reliable in the site's harsh weather conditions and has improved pH regulation of the ponds before water is released to the downstream rivers. The alternating-silo logic and mechanical discharge address the two issues that typically undermine lime systems: material ageing in storage and irregular extraction.
No case study should be read as a universal guarantee — every site has its own water chemistry, climate and operating constraints. But the project illustrates a principle that holds broadly: reliable pH control starts with reliable powder handling.
Key Takeaways for MENA Region Projects
The Gulf and wider MENA region present a very different climate from a northern mine site, yet the underlying lime-handling issues are the same — and in some respects more acute.
- pH management in wastewater treatment plants (STPs/WWTPs). Lime is widely used for pH correction, sludge conditioning and stabilisation. A dosing interruption can affect both effluent compliance and downstream sludge treatment.
- Remineralisation of desalinated water. Desalinated water is typically remineralised before distribution, and lime-based processes (often combined with CO2) are one of the established routes. Here, the accuracy and continuity of lime dosing directly affect final water quality.
- Heat and humidity. High ambient temperatures and coastal humidity increase the risk of caking and moisture uptake in hydrated lime. Silo design, discharge technology and stock rotation deserve particular attention.
- Redundancy for critical assets. For large utilities, a twin-silo configuration with automatic alternation provides both continuity of service and a natural maintenance window.
As the regional representative of Sodimate, Soditech can help EPC contractors and plant owners in the UAE, Saudi Arabia and across the MENA region define a lime storage and dosing configuration suited to their process and site conditions, with the technical support of the manufacturer.
Sources: Sodimate (sodimate.com); project summary "pH Regulation with Lime Feed System", Pollution Solutions Online. Site details have been anonymised.
Résumé en français — l'article complet est disponible en anglais (bouton EN).
Les eaux acides et chargées en métaux sont l'un des héritages les plus durables de l'activité minière. Elles doivent être neutralisées avant tout rejet, et la chaux reste le réactif de référence — à condition de pouvoir la stocker, l'extraire et la doser de façon fiable.
Le projet en bref
Sur un ancien site minier d'or et d'argent soumis à un climat rude, les eaux collectées dans des bassins devaient voir leur pH corrigé avant rejet en rivière. L'équipement fabriqué par Sodimate comprend deux silos de stockage équipés de désarcheurs mécaniques, une vis doseuse volumétrique, un convoyeur incliné et un réservoir de préparation de lait de chaux à environ 15 %.
Chaque silo dispose de trois détecteurs de niveau (haut, moyen, bas). Lorsque les deux silos sont pleins et que l'un atteint son niveau moyen, l'exploitation bascule sur le silo le plus plein, afin de limiter le temps de séjour de la chaux et donc les risques de mottage et de voûtage.
Selon le résumé publié du projet, l'installation a démontré sa fiabilité malgré les conditions climatiques et a amélioré la régulation du pH des bassins avant rejet.
Ce qu'il faut retenir pour la région MENA
Correction du pH en STEP, reminéralisation de l'eau dessalée, chaleur et humidité favorisant le mottage : les mêmes principes s'appliquent dans le Golfe. Une configuration double silo avec alternance automatique offre continuité de service et redondance. Soditech, représentant régional de Sodimate, accompagne les EPC et exploitants aux Émirats, en Arabie saoudite et dans toute la région.